First hour rating for tanks, gpm and Btu for tankless, yearly cost by type

To size a water heater, add up the hot water your home uses in its busiest hour and pick a tank whose first hour rating meets that total, using DOE's figures of 20 gallons per shower and 7 per dishwasher load. For a tankless unit, add the gpm of fixtures running at once and multiply by the temperature rise: 3.25 gpm heated from 50°F to 120°F needs about 118,400 Btu/h of gas input at 95% efficiency.

✅

Last updated October 2026

Method: Tanks: DOE's peak-hour worksheet, compared with the median first hour rating of DOE-certified models by size and fuel. Tankless: total gpm × 494.4 × temperature rise (8.24 lb per gallon × 60 minutes) gives Btu/h, divided by efficiency for gas or by 3,412 for kW. Yearly energy follows DOE's test formula, 365 × gallons per day × 8.24 × 67 ÷ UEF.

Included: Six household uses with DOE gallons, first hour ratings of 522 certified tank models, federal and WaterSense fixture flows, inlet temperatures for ten reference cities from NOAA normals and USGS, gas and electric tankless sizing with amperage, and yearly costs for four heater types at EIA prices.

Not included: Solar and combination space-heating systems, recirculation loops, pipe heat loss, venting and gas line sizing, installation cost, and rebates. Confirm the exact model's rating on its EnergyGuide label.

🚿 What are you sizing?

⏱️ Your busiest hour

Count what happens in the single hour when your home uses the most hot water (DOE peak-hour worksheet).

🚿 Peak-hour demand = first hour rating you need

70gallons
Look for a first hour rating of 70 gallons or more
DOE draw pattern
Medium usage
Rated daily use for that pattern
55 gal/day

📊 Which tank sizes reach 70 gallons?

Median first hour rating of DOE-certified models, with the middle half of models in brackets.

Type and sizeMedian FHRVerdict
Electric resistance, 30 gal46 (42 to 50)Too small
Electric resistance, 40 gal54 (51 to 57)Too small
Electric resistance, 50 gal63 (60 to 67)Too small
Gas, 30 gal62 (52 to 67)Too small
Gas, 40 gal70 (65 to 78)Typical model meets it
Gas, 50 gal82 (78 to 86)Typical model meets it
Heat pump, 40 gal60 (46 to 65)Too small
Heat pump, 50 gal69 (65 to 69)Too small
Heat pump, 65 gal80 (79 to 80)Typical model meets it
Heat pump, 80 gal91 (87 to 91)Typical model meets it

Always confirm the exact model: the first hour rating is printed on the EnergyGuide label as "Capacity (first hour rating)", or in the product literature for heat pump models, which are exempt from that label.

📋 Your peak hour, step by step

  • Showers: 3 x 20 gal60 gal
  • Hand dishwashing or food prep: 1 x 3 gal3 gal
  • Dishwasher loads: 1 x 7 gal7 gal
  • Peak-hour demand70 gal

💵 Yearly operating cost by type

DOE formula: 365 x gallons per day x 8.24 x 67 / UEF. The draw pattern follows your result; tap another to compare.

Electric tank UEF 0.92$611 (3,531 kWh)
Heat pump water heater UEF 3.75$150 (866 kWh)
Gas tank UEF 0.64$256 (173 therms)
Gas tankless (condensing) UEF 0.95$173 (117 therms)

Planning estimate. Per-use gallons come from the DOE peak-hour worksheet, test conditions and the annual energy formula from DOE's test procedure (58°F in, 125°F out), and prices from EIA 2025 averages. Gas units also use some electricity for fans and controls, which is not included. A licensed plumber should confirm venting, gas line and breaker sizes.

Water heater size calculator: tank and tankless sizing explained

A water heater size calculator answers a different question for each technology. A tank is sized by how much hot water it can deliver in your busiest hour, its first hour rating. A tankless heater has no reserve, so it is sized by the flow of every fixture running at once and by how much it has to warm the incoming water. Three showers, a dishwasher load and some food prep need a 70-gallon first hour rating; one shower and one faucet on a tankless unit need 3.25 gpm through a 70°F rise.

The fuel decides the running cost as much as the size does. The Electricity Cost Calculator and the Natural Gas Cost Calculator turn kWh and therms into a bill, and the BTU Calculator covers space heating, which a combination system would share with your hot water.

How DOE estimates peak-hour demand

DOE's sizing method starts with your busiest hour of the day, usually the morning shower rush or the evening cleanup. Count how many times each use happens in that hour, multiply by the average gallons of hot water per use, and add. The total is your peak-hour demand, and the tank's first hour rating should at least match it. These are the per-use figures from DOE's Energy Saver worksheet:

UseGallons of hot water per use (DOE)
Shower20
Shave2
Hand dishwashing or food prep3
Dishwasher load7
Top-loader washer load25
Front-loader (H-axis) washer load15

The worksheet estimates one hour, not a whole day. DOE also notes that its figures are averages; a long shower under an old showerhead can use more than 20 gallons, and a quick one under a WaterSense head far less. If you know your habits, adjust the counts rather than the gallons.

Worked example: a family's morning rush

A family of four runs three showers, one round of food prep and one dishwasher load in its busiest morning hour:

3 × 20 + 1 × 3 + 1 × 7 = 60 + 3 + 7 = 70 gallons Required first hour rating ≥ 70 gallons

Now compare with real equipment. The median DOE-certified 40-gallon gas tank has a first hour rating of exactly 70 gallons, and the median 50-gallon gas tank 82, so a typical gas model of either size works. On the electric side, the median 50-gallon resistance tank reaches only 63 gallons, and the median 50-gallon heat pump model 69, just short; the median 65-gallon heat pump model, at 80 gallons, clears it. A first hour rating of 70 falls in DOE's medium draw pattern (51 up to 75 gallons), which is rated at 55 gallons of hot water a day. These are the calculator's default inputs.

First hour ratings by tank size and fuel

Tank size and first hour rating are not the same thing: a powerful gas burner refills a 40-gallon tank faster than an electric element refills a 50-gallon one. We pulled all 5,102 consumer water heater listings in DOE's Compliance Certification Database (updated September 25, 2026), removed duplicate brand listings, and grouped the 522 unique storage models in common sizes by nominal size, counting electric tanks with a UEF of 1.5 or more as heat pumps:

TypeNominal sizeModelsMedian first hour ratingMiddle half of modelsMedian UEF
Electric resistance30 gal4846 gal42 to 50 gal0.92
Electric resistance40 gal8454 gal51 to 57 gal0.92
Electric resistance50 gal5363 gal60 to 67 gal0.92
Gas30 gal3562 gal52 to 67 gal0.60
Gas40 gal9170 gal65 to 78 gal0.64
Gas50 gal10082 gal78 to 86 gal0.65
Heat pump40 gal960 gal46 to 65 gal3.55
Heat pump50 gal3869 gal65 to 69 gal3.75
Heat pump65 gal2880 gal79 to 80 gal3.90
Heat pump80 gal3691 gal87 to 91 gal4.00

Three patterns stand out. Gas tanks deliver about 15 to 20 gallons more in the first hour than electric resistance tanks of the same size. Heat pump models need a bigger tank to match a gas unit, because the compressor heats slowly. And no electric resistance tanks above 55 gallons appear in the electric storage class at all: the federal standard for those sizes already requires heat pump efficiency, and the only exception is a separate grid-enabled class built for utility load-control programs.

How to size a tankless water heater

A tankless or demand heater warms water only as it flows, so DOE sizes it by flow rate and temperature rise. List the fixtures you expect to use at the same time, add their gallons per minute, and subtract the incoming water temperature from the output you want, normally 120°F. The heat output then follows from the weight and specific heat of water:

Output (Btu/h) = gpm × 8.24 lb/gal × 60 min × rise (°F) = gpm × 494.4 × rise Gas input (Btu/h) = output ÷ efficiency Electric (kW) = output ÷ 3,412    Amps = kW × 1,000 ÷ 240

The 8.24 lb per gallon is the density of water at 125°F used in DOE's test procedure; the familiar shortcut of 500 per gpm per degree rounds it up by about 1%. The flows you add come from the fixtures themselves. Federal rules cap them, and WaterSense models go lower:

FixtureFederal maximumWaterSense maximumNotes
Showerhead2.5 gpm at 80 psi2.0 gpmDOE's sizing example uses 2.5 gpm
Bathroom faucet2.2 gpm at 60 psi1.5 gpmEPA has proposed 1.2 gpm for WaterSense
Kitchen faucet2.2 gpm at 60 psino labelWaterSense labels bathroom and bar faucets only
Low-flow faucet--0.75 gpm in DOE's example
Tub, washer, dishwashernot regulated-Time a bucket fill for one minute

Worked example: DOE's shower-and-faucet case

DOE's own example runs a 0.75 gpm faucet and a 2.5 gpm shower together, so the heater must deliver 3.25 gpm. Incoming water at the default 50°F heated to 120°F is a 70°F rise. The output is 3.25 × 494.4 × 70 = 112,476 Btu/h. A condensing gas unit at 95% efficiency needs 112,476 ÷ 0.95 = 118,396 Btu/h of input, comfortably inside a 140,000 Btu/h model, which delivers 3.84 gpm at that rise. An electric unit needs 112,476 ÷ 3,412 = 33.0 kW, or 137.4 amps at 240 volts, which only the largest whole-house electric models reach.

Climate changes the answer. Move the same family to Minneapolis, give them two 2.0 gpm WaterSense showers at once, and the inlet water averages about 49°F: 4.0 gpm through a 71°F rise is 140,410 Btu/h, so a 140,000 Btu/h gas unit falls just short (3.79 gpm) and a 160,000 Btu/h unit is the smallest that fits. In Houston, with 73°F inlet water, the same 4.0 gpm needs only 92,947 Btu/h.

Inlet water temperature by region

DOE's default of 50°F is a reasonable guess for much of the country, but the real figure ranges from the low 40s to about 80°F. USGS found that groundwater 30 to 60 feet down runs 2 to 3°F above the mean annual air temperature, so the calculator adds 2.5°F to each reference city's NOAA 1991-2020 normal and rounds to a whole degree:

Reference cityMean annual air temp (NOAA)Estimated inlet waterRise to 120°FGas input for 5 gpmElectric for one 2.5 gpm shower
Duluth, MN40.6°F43°F77°F200,362 Btu/h27.9 kW
Minneapolis, MN46.9°F49°F71°F184,749 Btu/h25.7 kW
Chicago, IL51.2°F54°F66°F171,739 Btu/h23.9 kW
St. Louis, MO57.4°F60°F60°F156,126 Btu/h21.7 kW
Washington, DC59.3°F62°F58°F150,922 Btu/h21.0 kW
Atlanta, GA63.6°F66°F54°F140,514 Btu/h19.6 kW
Dallas-Fort Worth, TX66.6°F69°F51°F132,707 Btu/h18.5 kW
Houston, TX70.5°F73°F47°F122,299 Btu/h17.0 kW
Phoenix, AZ75.6°F78°F42°F109,288 Btu/h15.2 kW
Miami, FL77.4°F80°F40°F104,084 Btu/h14.5 kW

A Duluth home needs almost twice the burner of a Miami home for the same 5 gpm. If your utility draws from a river or lake rather than wells, winter water can be colder than this table, close to the monthly air temperature, so a thermometer under a cold tap in January is the best input.

What common tankless sizes deliver

Turning the formula around shows the flow a given heater can sustain: maximum gpm = input × efficiency ÷ (494.4 × rise). The middle column uses DOE's 70°F default rise and the right column Houston's 47°F:

Heater sizeFlow at a 70°F rise (50°F in)Flow at a 47°F rise (Houston, 73°F in)Current at 240 V
Gas, 140,000 Btu/h input3.84 gpm5.72 gpm-
Gas, 160,000 Btu/h input4.39 gpm6.54 gpm-
Gas, 180,000 Btu/h input4.94 gpm7.36 gpm-
Gas, 199,000 Btu/h input5.46 gpm8.14 gpm-
Electric, 18 kW1.77 gpm2.64 gpm75.0 A
Electric, 24 kW2.37 gpm3.52 gpm100.0 A
Electric, 27 kW2.66 gpm3.96 gpm112.5 A
Electric, 36 kW3.55 gpm5.29 gpm150.0 A

The electric rows explain DOE's remark that electric demand heaters typically manage about 2 gpm at a 70°F rise, against roughly 5 gpm for gas. They also show the electrical cost of going tankless with electricity: a 27 kW unit draws 112.5 amps, more than many older homes have spare.

Yearly operating cost: electric, gas or heat pump

DOE rates every water heater with a uniform energy factor (UEF) measured under one of four draw patterns, and its test procedure turns that into yearly energy: 365 days × gallons per day × 8.24 lb per gallon × 67°F (58°F in, 125°F out) ÷ UEF. The table applies that formula with EIA's 2025 residential averages of 17.30 cents per kWh and $1.48 per therm:

DOE draw patternHot water per dayElectric tank (UEF 0.92)Heat pump water heater (UEF 3.75)Gas tank (UEF 0.64)Gas tankless (condensing) (UEF 0.95)
Very small10 gal$111 (642 kWh)$27 (157 kWh)$47 (31 therms)$31 (21 therms)
Low38 gal$422 (2,439 kWh)$104 (598 kWh)$177 (120 therms)$119 (81 therms)
Medium55 gal$611 (3,531 kWh)$150 (866 kWh)$256 (173 therms)$173 (117 therms)
High84 gal$933 (5,392 kWh)$229 (1,323 kWh)$391 (264 therms)$264 (178 therms)

The UEFs are the medians of DOE-certified 50-gallon models for electric (0.92) and heat pump (3.75) tanks, the 40-gallon gas median (0.64), and the ENERGY STAR floor for gas tankless (0.95). At medium use, a heat pump water heater saves about $461 a year over an electric tank. Gas units also use a little electricity for fans and controls, which the comparison leaves out.

How to use this calculator

  1. Choose Tank or Tankless. Tank mode sizes by the first hour rating, tankless mode by flow and temperature rise.
  2. Tank: enter how many showers, shaves, dishwasher loads and washer loads happen in your busiest hour. The result is the first hour rating to look for, with a verdict for every common tank size and fuel.
  3. Tankless: set each fixture's flow and how many run at once, then pick your region's inlet temperature or enter a measured one. The result gives gas input, electric kW and amps, and which common sizes keep up.
  4. Compare running costs in the bottom card. The draw pattern follows your result; tap another pattern or change the prices to match your bills.

It is meant for homeowners replacing a failed heater who want to avoid buying too small, buyers weighing a heat pump or tankless upgrade, and plumbers who need a quick, sourced number to show a client.

Key terms

  • First hour rating (FHR): gallons of hot water a tank delivers in one hour starting fully heated, printed on the EnergyGuide label.
  • Peak-hour demand: the hot water your home uses in its busiest hour; the FHR should match or beat it.
  • Gallons per minute (gpm): flow rate; a tankless heater's rated maximum GPM is measured at a 67°F rise.
  • Temperature rise: output temperature minus incoming water temperature.
  • Uniform energy factor (UEF): DOE's efficiency rating, hot water energy delivered divided by energy used.
  • Draw pattern: one of DOE's four test profiles (very small, low, medium, high), chosen from the FHR or maximum GPM.

What changes the result

  • Back-to-back showers. Each adds 20 gallons to the peak hour; a fourth shower moves 70 gallons to 90.
  • Washer type. A top-loader adds 25 gallons, a front-loader 15.
  • Inlet temperature. Heating 5 gpm needs 200,362 Btu/h of gas input in Duluth and 104,084 Btu/h in Miami.
  • Output temperature. Raising it from 120°F to 140°F for a dishwasher without its own heater turns a 70°F rise into 90°F, about 29% more burner.

Limitations

The per-use gallons are DOE averages, and DOE's own worksheet example (three showers, a shave and hand dishwashing) is printed with a total of 66 gallons although the listed items add to 65; this page uses the itemized figures. Median first hour ratings describe typical models, not yours, so read the label before you buy. Tankless sizing assumes full fixture flow at 120°F, which is conservative for showers that mix in cold water. Yearly costs use DOE's standard test conditions and national average prices, so a cold-climate home with expensive power will pay more.

Related calculators

Size the rest of the home's heating with the BTU Calculator, cut the heat load with the Insulation Calculator, and check whether your panel can carry an electric unit with the Watts to Amps Calculator. The Electricity Cost Calculator and Natural Gas Cost Calculator price the yearly energy, and the Celsius to Fahrenheit Converter helps with metric spec sheets.

Sources

⚠️ Common mistakes & edge cases

Shopping by tank gallons

A 50-gallon label says nothing about recovery. The median DOE-certified 50-gallon electric tank delivers 63 gallons in its first hour while the median 40-gallon gas tank delivers 70. Compare first hour ratings, which DOE recommends and the EnergyGuide label prints.

Sizing a tankless heater for a summer inlet temperature

A unit that keeps up in August can run lukewarm in January when the supply water is colder. Size for the coldest month: in the Minneapolis example, a 140,000 Btu/h unit is short by 0.21 gpm, while a 160,000 Btu/h unit covers the same two showers.

Forgetting the electrical service

Electric tankless heaters are rated in kilowatts, and the amps add up fast: 18 kW is 75 amps and 36 kW is 150 amps at 240 volts. ENERGY STAR heat pump water heaters, by contrast, are capped at a maximum current rating of 24 amps, so check the panel before committing to electric tankless.

Counting bathrooms instead of simultaneous fixtures

A house with three bathrooms rarely runs three showers at once, and a one-bath house can still run a shower, a washer and a kitchen faucet together. Count what actually runs in the same minute, because that is the flow the heater must sustain.

Setting the thermostat to 140°F by default

DOE recommends 120°F for most uses and warns that 140°F increases the risk of scalding. A higher setting also raises standby losses. Use 140°F only when a dishwasher without its own heater needs it.

Ignoring where a heat pump unit will sit

A heat pump water heater pulls heat from the surrounding air, so a closet with no airflow or an unheated space that gets very cold hurts its performance. Check the manufacturer's installation clearances and temperature range before choosing one.

Note: Results are planning estimates. Gas line sizing, venting and electrical work follow local code, so have a licensed plumber or electrician confirm the installation.

❓ Frequently asked questions

What size water heater do I need?

Size a tank by its first hour rating, not its gallons. Add up the hot water your home uses in its busiest hour using DOE's figures (20 gallons per shower, 7 per dishwasher load, 25 per top-loader load) and buy a model whose first hour rating meets that total. Three showers, one dishwasher load and some food prep add up to 70 gallons, which a typical 40-gallon gas tank or 65-gallon heat pump model covers.

What is a first hour rating?

The first hour rating (FHR) is DOE's estimate of the maximum hot water a tank heater can deliver in one hour, starting fully heated. It depends on the tank size and on how fast the burner or element reheats. You find it on the yellow EnergyGuide label as "Capacity (first hour rating)" (heat pump models are exempt from that label, so check their product literature), and DOE's test measures it at a 125°F outlet temperature.

How do I size a tankless water heater?

Add the flow rates of the fixtures that run at the same time, then find the temperature rise: desired output minus incoming water temperature. DOE's example is a 0.75 gpm faucet plus a 2.5 gpm shower, or 3.25 gpm, with 50°F water heated to 120°F, a 70°F rise. That load needs 112,476 Btu/h of heat, or a gas unit of about 118,400 Btu/h input at 95% efficiency.

How many gallons per minute do I need for a tankless water heater?

Count fixtures, not bathrooms. A federally compliant showerhead flows at most 2.5 gpm and a WaterSense model 2.0 gpm; bathroom and kitchen faucets flow at most 2.2 gpm, and WaterSense bathroom faucets 1.5 gpm. Two WaterSense showers at once need 4.0 gpm; add a kitchen faucet at 2.2 gpm and the heater must deliver 6.2 gpm.

Can an electric tankless water heater supply a whole house?

Only with a large electrical service, especially in cold climates. Heating 2.5 gpm through a 70°F rise takes 25.4 kW, and DOE notes that electric demand heaters typically manage about 2 gpm at that rise. A 36 kW unit draws 150 amps at 240 volts and delivers 3.55 gpm at a 70°F rise, so check your panel before choosing electric.

What groundwater temperature should I use?

DOE says to assume 50°F unless you know otherwise. A better estimate comes from USGS, which found that groundwater 30 to 60 feet down runs 2 to 3°F above the mean annual air temperature. With NOAA normals that puts Duluth near 43°F, Chicago near 54°F, Atlanta near 66°F and Miami near 80°F. Surface water supplies get colder than this in winter, so measure at a cold tap in January if you can.

Is a 40-gallon or 50-gallon water heater better for a family of four?

It depends on the peak hour and the fuel. A family of four with three back-to-back showers and a dishwasher load needs about 70 gallons in its busiest hour. The median DOE-certified 40-gallon gas tank delivers 70 gallons and the 50-gallon gas tank 82, but the median 50-gallon electric tank delivers only 63, so electric households usually need a heat pump model of 65 gallons or more.

How much does it cost to run a water heater per year?

Using DOE's test formula and EIA's 2025 average prices (17.30 cents per kWh, $1.48 per therm), a medium-use household of 55 gallons a day pays about $611 a year with an electric tank, $256 with a gas tank, $173 with a condensing gas tankless unit and $150 with a heat pump water heater.

Are heat pump water heaters worth it?

They use about a quarter of the electricity of a resistance tank: the median DOE-certified 50-gallon heat pump model has a UEF of 3.75 against 0.92. At 55 gallons a day that is 866 kWh instead of 3,531 kWh, a saving of about $461 a year at 17.30 cents. They need a space that stays within the manufacturer's temperature range and room for air to circulate.

Will electric water heaters have to be heat pumps?

For most sizes, starting in 2029. Under 10 CFR 430.32, electric storage water heaters of 20 to 55 gallons made on or after May 6, 2029 must reach a UEF of 2.30, and those of 55 to 120 gallons 2.50, levels that only heat pump models achieve. Small 20 to 35 gallon units in the lightest draw patterns keep a lower standard. Most tanks over 55 gallons already need heat pump efficiency today.

💡 Good to know

The 2029 electric water heater standard

From May 6, 2029, most electric storage water heaters of 20 to 55 gallons must reach a UEF of 2.30, a level only heat pump models meet. If you are replacing an electric tank now, a heat pump model already saves about $461 a year at medium use.

ENERGY STAR sets a first hour floor

To earn the label, a heat pump water heater must deliver at least 45 gallons in its first hour and a gas tank at least 51 gallons, while a gas tankless model must supply 2.8 gpm or more at a 67°F rise with a UEF of at least 0.95.

Rated daily use is a test standard, not a forecast

DOE tests every model at 10, 38, 55 or 84 gallons a day, depending on its first hour rating or flow. A household that uses less hot water than its draw pattern spends less than the cost table shows, and a bigger one spends more.