Voltage Drop Calculator
Check the % drop on a copper or aluminum wire run against the 3% guideline
Last updated October 2026
Method: Vd = 2 × L × I × R ÷ 1,000 for single phase or two-wire DC and √3 × L × I × R ÷ 1,000 for three phase, with direct-current resistance at 75°C from NFPA 70 (NEC), 2023 edition, Chapter 9, Table 8 (stranded copper and aluminum). The 3% branch and 5% total targets come from the informational notes to 210.19(A) and 215.2(A), which are recommendations rather than requirements.
Included: Volts dropped, percent drop, voltage at the load, the 3% check, the next larger size that passes, the longest run at 3%, and a table across copper 14 AWG to 4/0 or aluminum 12 AWG to 4/0.
Not included: Ampacity and derating, conduit fill, conductor temperatures above 75°C, reactance and power factor on large AC feeders, and harmonics. Results are planning estimates, not a code-compliant design.
๐ Circuit details
Distance from the panel to the load (one way). The formula already doubles it for the return conductor.
โก Voltage drop
A drop of 4.95% is more than the 3% the NEC recommends for a branch circuit. Moving up to 8 AWG copper would bring it to 3% or less.
๐ Run summary
๐ Drop by wire size
Same voltage, current, distance, phase and material; only the wire size changes. Rows over 3% are red.
| Size | ฮฉ/1000 ft | Drop (V) | Drop (%) |
|---|---|---|---|
| 14 AWG | 3.140 | 9.42 | 7.85% |
| 12 AWG (selected) | 1.980 | 5.94 | 4.95% |
| 10 AWG | 1.240 | 3.72 | 3.10% |
| 8 AWG | 0.778 | 2.33 | 1.95% |
| 6 AWG | 0.491 | 1.47 | 1.23% |
| 4 AWG | 0.308 | 0.92 | 0.77% |
| 2 AWG | 0.194 | 0.58 | 0.48% |
| 1/0 AWG | 0.122 | 0.37 | 0.31% |
| 2/0 AWG | 0.0967 | 0.29 | 0.24% |
| 3/0 AWG | 0.0766 | 0.23 | 0.19% |
| 4/0 AWG | 0.0608 | 0.18 | 0.15% |
Voltage drop calculator: everything you need to know
A voltage drop calculator finds how many volts a wire loses over its run with Vd = 2 × L × I × R ÷ 1,000 (single phase). Example: 12 AWG copper carrying 15 A at 120 V over 100 feet drops 5.94 V, a 4.95% loss, well over the 3% the National Electrical Code recommends. 10 AWG still drops 3.10%, so the run needs 8 AWG (1.95%). The calculator shows the volts dropped, the percent drop, the voltage at the load and the first size that passes, for copper or aluminum.
How voltage drop is calculated
For a single-phase circuit, or a two-wire DC circuit, the calculator uses the standard formula:
Vd = 2 × L × I × R ÷ 1000 where L is the one-way distance in feet, I is the load current in amps, and R is the conductor resistance in ohms per 1,000 feet from NEC Chapter 9, Table 8. The 2 accounts for current traveling out on one conductor and back on the other. For a balanced three-phase circuit the 2 is replaced by the square root of 3, about 1.732. The percent drop is the volts dropped divided by the system voltage, times 100.
A worked example, step by step
Take a 120 V, 20 A single-phase circuit running 150 feet on 10 AWG copper (R = 1.24 ohms per 1,000 ft):
- Volts dropped: 2 × 150 × 20 × 1.24 ÷ 1,000 = 7.44 V.
- Percent drop: 7.44 ÷ 120 × 100 = 6.20%, about twice the 3% guideline.
- Voltage at the load: 120 − 7.44 = 112.56 V.
8 AWG (R = 0.778) still drops 4.67 V or 3.89%, so the run needs 6 AWG copper (R = 0.491): 2.95 V, or 2.46%. The calculator runs the same comparison automatically and names the first size that passes.
Voltage drop by wire size and distance
This matrix shows the percent voltage drop for a 240 V, 20 A single-phase circuit on copper as the size and the one-way run change. Red cells are over the 3% guideline; read down a column to see how far each size reaches before it fails.
| AWG (Cu) | 50 ft | 100 ft | 150 ft | 200 ft | 250 ft | 300 ft |
|---|---|---|---|---|---|---|
| 14 | 2.62% | 5.23% | 7.85% | 10.47% | 13.08% | 15.70% |
| 12 | 1.65% | 3.30% | 4.95% | 6.60% | 8.25% | 9.90% |
| 10 | 1.03% | 2.07% | 3.10% | 4.13% | 5.17% | 6.20% |
| 8 | 0.65% | 1.30% | 1.95% | 2.59% | 3.24% | 3.89% |
| 6 | 0.41% | 0.82% | 1.23% | 1.64% | 2.05% | 2.46% |
| 4 | 0.26% | 0.51% | 0.77% | 1.03% | 1.28% | 1.54% |
| 2 | 0.16% | 0.32% | 0.48% | 0.65% | 0.81% | 0.97% |
| 1/0 | 0.10% | 0.20% | 0.30% | 0.41% | 0.51% | 0.61% |
Stranded copper at 75°C (NEC Chapter 9, Table 8). At 120 V the same volts lost are twice the percent, so halve the reach; at other currents the drop scales in direct proportion.
What counts as acceptable voltage drop
For ordinary branch circuits and feeders the National Electrical Code does not set a mandatory maximum (a few special systems, such as fire pumps under Article 695, do). Its informational notes to 210.19(A) and 215.2(A) recommend keeping voltage drop to about 3% on a branch circuit and no more than 5% total for the feeder and branch circuit combined, which the code describes as providing reasonable efficiency of operation. Staying under 3% keeps motors, electronics, lighting and chargers close to their rated voltage. This calculator uses the 3% branch-circuit figure as its pass/fail line.
How far can you run each wire size?
This quick reference gives the maximum one-way run in feet that keeps a single-phase copper circuit at or under 3% for common voltage and current pairs, rounded down to the whole foot. Beyond these lengths, size up.
| AWG (Cu) | 120 V, 15 A | 120 V, 20 A | 240 V, 20 A | 240 V, 30 A |
|---|---|---|---|---|
| 14 | 38 ft | 28 ft | 57 ft | 38 ft |
| 12 | 60 ft | 45 ft | 90 ft | 60 ft |
| 10 | 96 ft | 72 ft | 145 ft | 96 ft |
| 8 | 154 ft | 115 ft | 231 ft | 154 ft |
| 6 | 244 ft | 183 ft | 366 ft | 244 ft |
| 4 | 389 ft | 292 ft | 584 ft | 389 ft |
| 2 | 618 ft | 463 ft | 927 ft | 618 ft |
| 1/0 | 983 ft | 737 ft | 1,475 ft | 983 ft |
Computed from the one-way limit L = 0.03 × V × 1,000 ÷ (2 × I × R). These lengths satisfy voltage drop only; always confirm the conductor's ampacity for the load first.
Copper vs. aluminum conductors
Aluminum conductors cost less and weigh less, which is why they are common for services and large feeders, but they have about 64% more resistance than copper of the same size. Table 8 lists 12 AWG aluminum at 3.25 ohms per 1,000 ft against 1.98 for copper, and 4/0 aluminum at 0.100 against 0.0608. In practice an aluminum run needs a conductor about two sizes larger to match copper's voltage drop. For example, a 240 V, 100 A feeder 150 ft long drops 1.53% on 1/0 copper and 1.99% on 2/0 aluminum; 4/0 aluminum brings it down to 1.25%. Switch the calculator's material to aluminum to run your own numbers. Aluminum terminations must be rated for it, a separate code requirement this tool does not check.
Why voltage drop matters
Every foot of wire has resistance, and resistance turns electrical energy into heat. On a short run that loss is negligible, but it grows with length and current. The consequences of too much drop include:
- Wasted energy: the power lost in the wire is heat you pay for but never use.
- Underperforming equipment: motors lose torque and run hot, heaters and chargers slow down, and pumps move less water.
- Flicker and failures: LED drivers and sensitive electronics can flicker, reset or wear out early on a sagging supply.
- Nuisance trips: motors drawing extra current to compensate can trip breakers or overloads.
How to use this voltage drop calculator
You need four numbers, a material and a phase. Work through the fields in order:
- System voltage: enter the nominal circuit voltage. Common choices are 120 V and 240 V for homes, 208, 277 or 480 V for commercial work and 12 V for low-voltage DC; use the quick buttons or type your own.
- Load current: enter the running amps of the load, not the breaker size. For motors, use the full-load amps from the nameplate.
- One-way distance: measure from the panel to the load along the actual cable route, in feet. The formula doubles it for you.
- Material and size: choose copper or aluminum, then the AWG size you plan to use. Smaller numbers mean thicker wire and less drop.
- Phase: single phase for typical residential circuits and for DC, three phase for balanced three-phase loads.
The result updates as you type. If the headline turns red, the drop is over 3%; the calculator names the first larger size that passes and lists the drop for every size so you can see the trade-offs.
Who this calculator is for
Anyone running a circuit far enough that the wire length matters, including:
- Homeowners and DIYers wiring a detached garage, shed, shop or backyard outlet.
- EV-charger installers sizing a 240 V run from the panel to a parking spot.
- Solar and off-grid builders checking long DC and AC runs between panels, inverters and loads.
- Pump and irrigation installers feeding a well pump hundreds of feet away.
- Apprentices and estimators checking a design before pulling or buying wire.
Three common scenarios
Voltage drop problems almost always come down to long runs at meaningful current. Three typical copper cases:
- Backyard shed, 120 V, 15 A, 120 ft: 12 AWG drops 5.94%, too much; 10 AWG still drops 3.72%, and 8 AWG brings it to 2.33%.
- EV charger, 240 V, 40 A, 150 ft: 8 AWG drops 3.89%, over the line; 6 AWG lands at 2.46% and passes.
- Well pump, 240 V, 10 A, 250 ft: 10 AWG drops 2.58%, acceptable, but at 350 ft the same wire reaches 3.62%, so distance alone can force an upsize.
Factors that change the result
- Distance: drop is directly proportional to length: double the run, double the drop.
- Current: also directly proportional, so a heavier load on the same wire drops more voltage.
- Wire size: the biggest lever you control. Each two-size step (14 to 12, 12 to 10 AWG) cuts resistance by about 37%, and each step between 1/0 and 4/0 by about 21%.
- System voltage: higher voltage means a smaller percent drop for the same volts lost, which is why 240 V tolerates longer runs than 120 V.
- Phase: three phase uses √3 instead of 2, so it shows less line-to-line drop than single phase at the same current.
- Material and temperature: aluminum and hotter conductors have higher resistance and more drop. Table 8 values are at 75°C.
3-phase voltage drop: single vs. three phase
A balanced three-phase load uses √3 (1.732) in place of the 2, so for the same current and run it shows less line-to-line drop. This table compares both for a 480 V, 30 A load over a 200 ft one-way copper run; switch the phase selector above to reproduce either column.
| AWG (Cu) | 1-phase drop | 1-phase % | 3-phase drop | 3-phase % |
|---|---|---|---|---|
| 14 | 37.68 V | 7.85% | 32.63 V | 6.80% |
| 12 | 23.76 V | 4.95% | 20.58 V | 4.29% |
| 10 | 14.88 V | 3.10% | 12.89 V | 2.68% |
| 8 | 9.34 V | 1.95% | 8.09 V | 1.68% |
| 6 | 5.89 V | 1.23% | 5.10 V | 1.06% |
| 4 | 3.70 V | 0.77% | 3.20 V | 0.67% |
| 2 | 2.33 V | 0.48% | 2.02 V | 0.42% |
| 1/0 | 1.46 V | 0.30% | 1.27 V | 0.26% |
Three-phase percentages are about 13.4% lower than single-phase for the same inputs (√3 ÷ 2 = 0.866). Three-phase drop uses the line-to-line voltage and assumes a balanced load.
Key electrical terms
- AWG (American Wire Gauge): the U.S. sizing system for wire. A smaller number is a thicker wire with lower resistance; sizes above 1 AWG are written 1/0, 2/0, 3/0 and 4/0.
- Ampacity: the maximum current a conductor can carry continuously under its conditions of use. It sets the minimum legal wire size before you consider voltage drop.
- Resistance (ohms per 1,000 ft): how much a conductor opposes current per thousand feet, the R in the formula.
- One-way vs. circuit length: one-way is panel to load; circuit length is the full out-and-back path. The formula multiplies one-way by 2.
- Branch circuit vs. feeder: a branch circuit supplies the final loads; a feeder supplies a subpanel. The 3% target is for the branch; 5% is the combined total.
- Single vs. three phase: single phase is the typical residential supply; three phase is common in commercial buildings and uses the √3 factor.
Tips to keep voltage drop in check
- Size up on long runs. If you are near the 3% line, the next larger size buys margin for little extra cost.
- Use the higher voltage where you can. At the same wattage a 240 V circuit draws half the current of a 120 V circuit, so its percent drop is a quarter as large on the same wire.
- Measure the real route. Include vertical runs, bends and detours; a straight-line measurement underestimates the length.
- Buy extra wire. Slack at both ends and routing around obstacles add length beyond the measured run.
- Check ampacity first, then drop. Pick the smallest wire that is legal for the current, then upsize only if the drop is too high.
Limitations and assumptions
- It uses Table 8 direct-current resistance at 75°C for stranded conductors; hotter conductors drop more.
- It does not model reactance, power factor or harmonics, which matter on large AC feeders and inductive loads (NEC Chapter 9, Table 9 covers AC impedance).
- It does not check ampacity, derating, conduit fill or termination ratings, all of which can require a larger wire than voltage drop alone.
- It assumes a balanced load on three phase and a steady current, not motor inrush or varying demand.
- Final sizing must follow the NEC edition your jurisdiction has adopted and any local amendments, verified by a licensed electrician for permitted work.
Related electrical calculators
This page answers "how much voltage will I lose on this run, and is the wire big enough for the drop?" For the neighboring questions:
- To pick a wire size from ampacity and length together, use the Wire Size Calculator.
- To check that the conductors fit the raceway, use the Conduit Fill Calculator.
- To turn a nameplate in watts or kVA into amps, use the Watts to Amps Calculator or the kVA to Amps Calculator.
- To work out volts, amps, ohms or watts on a circuit, use the Ohm's Law Calculator.
Voltage drop and Ohm's law
Voltage drop is Ohm's law applied to the wire itself. Ohm's law says V = I × R: the voltage across any resistance equals the current through it times that resistance. The conductor between your panel and the load is a resistor, so the voltage it uses up is the current times the round-trip wire resistance. That is exactly what the formula computes: the × 2 (or √3) and the ÷ 1,000 convert one-way feet and ohms per 1,000 ft into the total resistance in the circuit. To explore the V = I × R relationship on its own, or to solve for power and resistance, the Ohm's Law Calculator handles the general case.
DC and low-voltage runs (12 V, 24 V, 48 V)
Low-voltage DC systems (RV and marine wiring, solar arrays, landscape lighting and battery banks) are where voltage drop bites hardest, because the percentage is measured against a small number. A 0.5 V drop is trivial on a 240 V circuit (0.21%) but a painful 4.17% on a 12 V system. A 12 V, 10 A load just 20 feet away drops 6.60% on 12 AWG copper and needs 8 AWG (2.59%) to stay within 3%. The single-phase formula with its × 2 factor applies directly to two-wire DC circuits; enter the nominal DC voltage, the load current and the one-way run. Table 8 values are DC resistances, so they apply exactly.
Sources
- National Fire Protection Association: NFPA 70, National Electrical Code (NEC), 2023 edition (adopted in most states; local adoption differs, so check which edition your jurisdiction enforces): Chapter 9, Table 8 (conductor properties, DC resistance at 75°C) and the voltage-drop informational notes to 210.19(A) and 215.2(A).
- The formulas are Ohm's law applied to the conductor loop (2 × L for single phase and DC, √3 × L for balanced three phase) and need no external data beyond Table 8.
โ ๏ธ Common mistakes & edge cases
Entering the round-trip length
The formula already doubles the one-way distance to count the return conductor. If you enter the full out-and-back length, you overstate the drop by 2x. Enter only the panel-to-load distance.
Using the breaker size instead of the load current
Voltage drop depends on the actual running current, not the breaker rating. A 20 A breaker feeding a 9 A load drops voltage based on 9 A. Use the real load (or motor full-load amps), not the overcurrent device.
Checking drop but skipping ampacity
A wire that passes the 3% check may still be illegal if it cannot carry the current. Confirm the conductor's ampacity (with any derating) first, then upsize for voltage drop if needed.
Treating aluminum like copper
Aluminum has about 64% more resistance than copper of the same size, so the same AWG drops noticeably more. Select aluminum in the calculator, or plan on a conductor about two sizes larger.
❓ Frequently asked questions
How is voltage drop calculated?
For a single-phase or two-wire DC circuit, voltage drop is Vd = 2 x L x I x R / 1000, where L is the one-way distance in feet, I is the load current in amps and R is the conductor resistance in ohms per 1,000 ft from NEC Chapter 9, Table 8. The 2 counts both the outgoing and the return conductor. For a balanced three-phase circuit you replace the 2 with the square root of 3 (about 1.732). Dividing the drop by the system voltage and multiplying by 100 gives the percent drop.
What is an acceptable voltage drop?
The National Electrical Code recommends, in informational notes to 210.19(A) and 215.2(A), keeping voltage drop to 3% on a branch circuit and to 5% for the feeder and branch circuit combined, for reasonable efficiency of operation. These notes are recommendations, not enforceable requirements, but they are the figures electricians and inspectors design to. This calculator flags any result over 3%.
Why does voltage drop matter?
Excess voltage drop wastes energy as heat in the wire and starves the load of voltage. Motors run hotter and lose torque, LED drivers can flicker, heaters and chargers run slowly, and sensitive electronics may misbehave. Long runs to a shed, well pump, EV charger or detached garage are the usual culprits.
Why do I enter the one-way distance instead of the total wire length?
Enter only the distance from the panel to the load. The formula already multiplies by 2 (single phase) to count the return conductor, so you do not double it yourself. If you measured the full round-trip length of wire, enter half of it.
How do I fix excessive voltage drop?
The most common fix is a larger conductor: a smaller AWG number has lower resistance. You can also shorten the run, reduce the load on the circuit, or use a higher voltage where the equipment allows it, since the same power at twice the voltage draws half the current. The calculator names the first larger size of the same material that brings the drop to 3% or less.
Does this calculator work for aluminum wire?
Yes. Switch the material to aluminum and it uses the NEC Chapter 9, Table 8 values for stranded aluminum. Aluminum has about 64% more resistance than copper of the same size (3.25 versus 1.98 ohms per 1,000 ft at 12 AWG), so an aluminum run usually needs a conductor about two sizes larger for the same drop. The aluminum list starts at 12 AWG because the NEC ampacity table (Table 310.16) lists no 14 AWG aluminum.
What is the difference between single-phase and three-phase voltage drop?
Single phase uses a multiplier of 2 (out and back). A balanced three-phase load uses the square root of 3, about 1.732, because of how the phase currents combine. For the same current, distance and wire, the line-to-line drop on three phase is about 13.4% lower than on single phase.
Does voltage drop affect the wire size I'm allowed to use?
Wire size is set first by ampacity: the conductor must be able to carry the load current under the NEC ampacity tables. Voltage drop is a separate, recommended check on top of that. A wire can be large enough for the current yet still drop too much voltage on a long run, in which case you upsize for the drop, not for the ampacity.
What resistance values does this calculator use?
NEC Chapter 9, Table 8 direct-current resistance at 75 degrees C, in ohms per 1,000 ft. Uncoated stranded copper: 14 AWG 3.14, 12 AWG 1.98, 10 AWG 1.24, 8 AWG 0.778, 6 AWG 0.491, 4 AWG 0.308, 2 AWG 0.194, 1/0 0.122, 2/0 0.0967, 3/0 0.0766, 4/0 0.0608. Stranded aluminum: 12 AWG 3.25, 10 AWG 2.04, 8 AWG 1.28, 6 AWG 0.808, 4 AWG 0.508, 2 AWG 0.319, 1/0 0.201, 2/0 0.159, 3/0 0.126, 4/0 0.100. Solid copper in sizes 14 to 8 AWG is slightly lower, for example 1.93 instead of 1.98 at 12 AWG.
Is this calculator a substitute for an electrician or the code?
No. It is a fast planning estimate. Final conductor sizing must satisfy ampacity, temperature, conduit fill and termination limits, and must follow the NEC edition your state or city has adopted plus any local amendments. For permitted work, have a licensed electrician confirm the design.
How far can I run 12 AWG wire without too much voltage drop?
For single-phase copper 12 AWG (1.98 ohms per 1,000 ft), the 3% guideline allows a one-way run of about 60 ft at 120 V and 15 A, 45 ft at 120 V and 20 A, and 90 ft at 240 V and 20 A. Past those lengths step up to 10 AWG or larger, or use a higher voltage.
What wire size do I need for a 20 amp circuit 100 feet away?
For voltage drop alone on copper: at 120 V, 12 AWG drops 6.60% and 10 AWG 4.13%, so you need 8 AWG (2.59%) to stay within 3%. At 240 V the same 20 A load needs only 10 AWG (2.07%). Check ampacity and the breaker size as well; the larger wire must also fit the device terminals.
How do you calculate three-phase voltage drop?
Use Vd = 1.732 x L x I x R / 1000, where 1.732 is the square root of 3, L is the one-way feet, I the amps and R the ohms per 1,000 ft. Example: a 480 V, 30 A load over 200 ft on 6 AWG copper drops about 5.10 V, or 1.06%, versus 5.89 V (1.23%) for the same run on single phase.
๐ก Good to know
Distance and current hit equally hard
Voltage drop is proportional to both the run length and the current. Doubling either one doubles the drop, which is why a modest load 200 feet out can need the same wire as a big load 100 feet out.
Higher voltage reaches farther
At the same wattage, a 240 V circuit carries half the current of a 120 V circuit, so it loses half the volts on the same wire, and those volts are a smaller share of the higher supply. Running 240 V where the equipment allows it is often cheaper than upsizing the conductor.
3% is a recommendation, not a rule
The NEC's 3% and 5% figures sit in informational notes, which the code treats as explanatory material rather than enforceable requirements. They are still the right design target: they keep equipment near its rated voltage and limit the energy lost in the wire.
Related Calculators
Wire Size Calculator
Copper or aluminum wire gauge for a load and run length
Conduit Fill Calculator
Conductor fill percentage per NEC Chapter 9 tables
Ohm's Law Calculator
Calculate voltage, current, resistance and power
kVA to Amps Calculator
Convert kVA to amps for single-phase and three-phase circuits
Watts to Amps Calculator
Convert watts to amps for DC and AC circuits
Solar Panel Calculator
System size, panel count and payback for home solar