๐Ÿ‡บ๐Ÿ‡ธ USC
Home & Construction
๐Ÿ”Œ

Voltage Drop Calculator

Check the % drop on a wire run against the 3% limit

โœ…

Last updated June 2026

Method: Voltage drop uses Vd = 2 × L × I × R / 1000 for single phase and √3 × L × I × R / 1000 for three phase, with copper resistance per 1000 ft from NEC Chapter 9, Table 8. The 3% / 5% targets follow the NEC informational notes on branch and feeder voltage drop.

Included: Voltage dropped, percent drop, voltage at the load, the 3% pass/fail check, a suggested heavier copper gauge, the maximum run at 3%, and a side-by-side table across all gauges.

Not included: Ampacity and derating checks, aluminum conductors, conduit-fill and temperature corrections, power factor, and harmonic effects. Results are planning estimates, not a code-compliant design.

๐Ÿ”Œ Circuit details

V
A
ft

Distance from the panel to the load (one way). The formula already doubles it for the return conductor.

โšก Voltage drop

4.83%
Over the 3% NEC-recommended limit
Voltage dropped
5.79 V
Voltage at the load
114.2 V
Conductor resistance
1.930 ฮฉ/kft
Recommended max (3%)
3.60 V
๐Ÿšจ Over the 3% limit

A drop of 4.83% exceeds the NEC-recommended 3% maximum for a branch circuit. Upsizing to AWG 8 copper would bring it back within range.

๐Ÿ“‹ Run summary

Wire
AWG 12 Cu
Phase
Single phase
Load / distance
15.0 A ยท 100 ft
Max run at 3%
62 ft

๐Ÿ“Š Drop by wire gauge

Same voltage, current, distance and phase โ€” only the copper gauge changes. Rows over 3% are flagged.

Gauge (AWG)ฮฉ/1000 ftDrop (V)Drop (%)
AWG 143.0709.217.68%
AWG 12 (selected)1.9305.794.83%
AWG 101.2103.633.03%
AWG 80.7642.291.91%
AWG 60.4911.471.23%
AWG 40.3080.920.77%
AWG 20.1940.580.48%
AWG 1/00.1220.370.31%
Estimate only โ€” not a substitute for a licensed electrician or the National Electrical Code. Values assume stranded copper at ~75ยฐC; aluminum, very high temperatures, conduit fill and power factor change the result. Size for the worst case and plan for ~10% extra wire on the spool to cover slack, splices and routing.

Voltage drop calculator: everything you need to know

A voltage drop calculator finds how many volts a wire loses over its run using Vd = 2 × L × I × R ÷ 1000 (single phase). Example: AWG 12 copper carrying 15 A at 120 V over 100 feet drops 5.79 V - a 4.8% loss, over the recommended 3% limit - so you upsize to AWG 10. This tool shows the volts dropped, the percent drop, the voltage reaching the load, and the next gauge that passes.

How voltage drop is calculated

For a single-phase circuit, the calculator uses the standard formula:

Vd = 2 × L × I × R ÷ 1000

where L is the one-way distance in feet, I is the load current in amps, and R is the conductor resistance in ohms per 1000 feet. The 2 accounts for current traveling out on one conductor and back on the other. For a balanced three-phase circuit, the 2 is replaced by the square root of 3 (about 1.732). The percent drop is simply the volts dropped divided by the system voltage, times 100.

A worked example, step by step

Take a 120 V, 20 A single-phase circuit running 150 feet on AWG 10 copper (R = 1.21 ohms per 1000 ft):

  • Volts dropped: 2 × 150 × 20 × 1.21 ÷ 1000 = 7.26 V.
  • Percent drop: 7.26 ÷ 120 × 100 = 6.05% - well over the 3% target.
  • Voltage at the load: 120 − 7.26 = 112.74 V.

To pass, you would jump to AWG 6 copper (R = 0.491), which drops only about 2.95 V or roughly 2.45%. The calculator runs that same comparison automatically and tells you which gauge to use.

Voltage drop by wire gauge and distance

This matrix shows the percent voltage drop for a 240 V, 20 A single-phase circuit as the copper gauge and one-way run change. Red cells are over the recommended 3% limit - read down a column to see how far each gauge reaches before it fails.

AWG (Cu) 50 ft100 ft 150 ft200 ft 250 ft300 ft
142.56%5.12%7.68%10.23%12.79%15.35%
121.61%3.22%4.83%6.43%8.04%9.65%
101.01%2.02%3.02%4.03%5.04%6.05%
80.64%1.27%1.91%2.55%3.18%3.82%
60.41%0.82%1.23%1.64%2.05%2.46%
40.26%0.51%0.77%1.03%1.28%1.54%
20.16%0.32%0.48%0.65%0.81%0.97%
1/00.10%0.20%0.30%0.41%0.51%0.61%

Assumes stranded copper at ~75°C. At 120 V the same volts lost are double the percent, so halve the reach; at other currents, drop scales in direct proportion.

What counts as acceptable voltage drop

The National Electrical Code does not mandate a maximum in most cases, but its informational notes recommend keeping voltage drop to about 3% on a branch circuit and no more than 5% total for the feeder and branch circuit combined. Staying under 3% keeps motors, electronics, lighting and chargers operating at their rated voltage. This calculator uses the 3% branch-circuit figure as its pass/fail threshold.

How far can you run each wire gauge?

This quick reference gives the maximum one-way run in feet that keeps a single-phase copper circuit at or under 3% for common voltage and current pairs. Beyond these lengths, size up a gauge.

AWG (Cu) 120 V, 15 A120 V, 20 A 240 V, 20 A240 V, 30 A
1439 ft29 ft59 ft39 ft
1262 ft47 ft93 ft62 ft
1099 ft74 ft149 ft99 ft
8157 ft118 ft236 ft157 ft
6244 ft183 ft367 ft244 ft
4390 ft292 ft584 ft390 ft
2619 ft464 ft928 ft619 ft
1/0984 ft738 ft1,475 ft984 ft

Computed from the one-way limit L = 0.03 × V × 1000 ÷ (2 × I × R). These lengths satisfy voltage drop only - always confirm the conductor's ampacity for the load first.

Why voltage drop matters

Every foot of wire has resistance, and resistance turns electrical energy into heat. On a short run that loss is negligible, but it grows with length and current. The consequences of too much drop include:

  • Wasted energy: the power lost in the wire is heat you pay for but never use.
  • Underperforming equipment: motors lose torque and run hot, heaters and chargers slow down, and pumps move less water.
  • Flicker and failures: LED drivers and sensitive electronics can flicker, reset, or wear out early on a sagging supply.
  • Nuisance trips: motors drawing extra current to compensate can trip breakers or overloads.

How to use this voltage drop calculator

You only need four numbers and a phase selection to get a realistic answer. Work through the fields in order:

  1. System voltage: enter the nominal circuit voltage. Common choices are 120 V and 240 V for homes, and 277 V or 480 V for commercial work - use the quick buttons or type your own.
  2. Load current: enter the running amps of the load (not the breaker size). For motors, use the full-load amps from the nameplate.
  3. One-way distance: measure from the panel to the load along the actual cable route, in feet. Enter the one-way length; the formula doubles it for you.
  4. Wire gauge: pick the copper AWG you plan to use. Smaller numbers mean thicker wire and less drop.
  5. Phase: choose single phase for typical residential circuits, or three phase for balanced three-phase loads.

Press Calculate and read the percent drop at the top. If it is highlighted red, it is over 3%; the calculator names the next gauge that passes and shows a full table so you can see the trade-offs across all sizes.

Who this calculator is for

This tool is built for anyone running a circuit far enough that the wire length matters. That includes:

  • Homeowners and DIYers wiring a detached garage, shed, shop, or backyard outlet.
  • EV-charger installers sizing a 240 V run from the panel to a parking spot.
  • Solar and off-grid builders checking long DC and AC runs between panels, inverters and loads.
  • Pump and irrigation installers feeding a well pump or pivot hundreds of feet away.
  • Apprentices and estimators sanity-checking a design before pulling wire or buying it.

Three common scenarios

Voltage drop problems almost always come down to long runs at meaningful current. Here are three typical cases:

  • Backyard shed, 120 V / 15 A / 120 ft: on AWG 12 the drop is about 5.8% - too much. AWG 8 brings it to roughly 2.3%.
  • EV charger, 240 V / 40 A / 150 ft: on AWG 8 the drop is about 3.8% - over the line; moving to AWG 6 lands near 2.5% and passes.
  • Well pump, 240 V / 10 A / 250 ft: on AWG 10 the drop is about 2.5% - acceptable - but at 350 ft the same wire climbs to roughly 3.5% and exceeds 3%, so distance alone can force an upsize.

Factors that change the result

Adjust the inputs and you will see a handful of factors dominate the outcome:

  • Distance: drop is directly proportional to length - double the run, double the drop.
  • Current: also directly proportional - a heavier load on the same wire drops more voltage.
  • Wire gauge: the biggest lever you control. Each step up in size cuts resistance by roughly 20-37%.
  • System voltage: higher voltage means a smaller percent drop for the same volts lost, which is why 240 V tolerates longer runs than 120 V.
  • Phase: three-phase uses √3 instead of 2, so it shows less line-to-line drop than single phase at the same current.
  • Conductor material and temperature: aluminum and hotter conductors have higher resistance and more drop (this tool assumes copper near 75 degrees C).

3-phase voltage drop calculator: single vs three phase

A three-phase balanced load uses √3 (1.732) in place of the 2, so for the same current and run it shows less line-to-line drop. This table compares both for a 480 V, 30 A load over a 200 ft one-way run - switch the phase selector above to reproduce either column.

AWG (Cu) 1-phase drop1-phase % 3-phase drop3-phase %
1436.84 V7.68%31.90 V6.65%
1223.16 V4.83%20.06 V4.18%
1014.52 V3.02%12.57 V2.62%
89.17 V1.91%7.94 V1.65%
65.89 V1.23%5.10 V1.06%
43.70 V0.77%3.20 V0.67%
22.33 V0.48%2.02 V0.42%
1/01.46 V0.30%1.27 V0.26%

Three-phase percentages are about 13.4% lower than single-phase for the same inputs (√3 ÷ 2). Three-phase drop uses the line-to-line voltage and assumes a balanced load.

Key electrical terms

  • AWG (American Wire Gauge): the U.S. sizing system for wire. Counterintuitively, a smaller number is a thicker wire with lower resistance.
  • Ampacity: the maximum current a conductor can carry safely. It sets the minimum legal wire size before you even consider voltage drop.
  • Resistance (ohms/1000 ft): how much a conductor opposes current per thousand feet. It is the R in the voltage-drop formula.
  • One-way vs. circuit length: one-way is panel-to-load; circuit length is the full out-and-back path. The formula multiplies one-way by 2.
  • Branch circuit vs. feeder: a branch circuit supplies the final loads; a feeder supplies a subpanel. The 3% target is for the branch; 5% is the combined total.
  • Single vs. three phase: single phase is the typical residential supply; three phase is common in commercial and industrial settings and uses the √3 factor.

Tips to keep voltage drop in check

  • Size up one gauge on long runs. If you are near the 3% line, the next size down in AWG number buys a comfortable margin for cheap insurance.
  • Use the higher voltage where you can. A 240 V circuit drops half the percent of a 120 V circuit at the same wattage, so it reaches much farther.
  • Route smart, but don't cheat the math. Measure the real cable path including vertical drops and bends; "as the crow flies" underestimates length.
  • Buy about 10% extra wire. Slack at both ends, splices, and routing around obstacles eat into a spool faster than you expect - order ~10% more than the straight-line estimate.
  • Check ampacity first, then drop. Pick the smallest wire that is legal for the current, then upsize only if the drop is too high.

Limitations and assumptions

This calculator is a fast planning estimate, not a finished design. Keep these assumptions in mind:

  • It assumes copper conductors at about 75 degrees C; aluminum and hotter conductors drop more.
  • It uses simple DC-style resistance and does not model reactance, power factor, or harmonics, which matter on large or inductive loads.
  • It does not check ampacity, derating, conduit fill, or termination temperature limits - all of which can require a larger wire than voltage drop alone.
  • It assumes a balanced load for three-phase and a single steady current, not motor inrush or varying demand.
  • Final sizing must follow the current edition of the National Electrical Code and any local amendments, verified by a licensed electrician for permitted work.

How it compares to related calculators

This page answers "how much voltage will I lose on this run, and is the wire big enough?" If you have a different project question, a sister tool fits better:

Wiring is just one part of a build - the rest of our construction tools estimate materials rather than electrical loads. Use the Concrete Calculator for a slab or footing, the Roofing Calculator for shingle squares, the Roof Pitch Calculator to turn rise-over-run into an angle, and the Paint Calculator for gallons of coverage. Reach for this voltage drop tool only when you are sizing conductors for a circuit run.

Voltage drop and Ohm's law

Voltage drop is just Ohm's law applied to the wire itself. Ohm's law says V = I × R: the voltage across any resistance equals the current through it times that resistance. The conductor between your panel and the load is a resistor, so the voltage it "eats" is the current times the round-trip wire resistance. That is exactly what the formula computes - the × 2 (or √3) and the ÷ 1000 simply convert one-way feet and ohms-per-1000-ft into the total resistance in the circuit. If you want to explore the V = I × R relationship on its own, or solve for power and resistance, the Ohm's Law Calculator handles the general case while this tool specializes it for long wire runs.

DC and low-voltage runs (12V, 24V, 48V)

Low-voltage DC systems - RV and marine wiring, solar arrays, landscape lighting, and 12V or 24V battery banks - are where voltage drop bites hardest, because the percentage is measured against a small number. A 0.5-volt drop is trivial on a 240 V circuit (0.2%) but is a painful 4.2% on a 12 V system. That is why off-grid and automotive installers often target a tighter 2-3% on DC and run surprisingly thick cable for modest currents. The single-phase formula in this calculator (with the × 2 factor for the out-and-back conductors) applies directly to two-wire DC circuits; just enter your nominal DC system voltage, the load current in amps, and the one-way run. The copper resistance values are the same whether the current is AC or DC at these gauges.

Sources

  • National Fire Protection Association (NFPA) - NFPA 70, National Electrical Code (NEC): branch-circuit and feeder voltage-drop informational notes (3% / 5%) and Chapter 9, Table 8 conductor properties.
  • NEC Chapter 9, Table 8 - direct-current resistance values for copper and aluminum conductors in ohms per 1000 ft, the basis for the resistances used here.
  • NEC Article 210.19 and 215.2 informational notes - recommended voltage drop on branch circuits and feeders.

โš ๏ธ Common mistakes & edge cases

Entering the round-trip length

The formula already doubles the one-way distance to count the return conductor. If you enter the full out-and-back length, you will overstate the drop by 2x. Enter only panel-to-load distance.

Using the breaker size instead of the load current

Voltage drop depends on the actual running current, not the breaker rating. A 20 A breaker feeding a 9 A load drops voltage based on 9 A. Use the real load (or motor full-load amps), not the overcurrent device.

Checking drop but skipping ampacity

A wire that passes the 3% drop test may still be illegal if it cannot carry the current. Always confirm the conductor's ampacity (with any derating) first, then upsize for voltage drop if needed.

Assuming aluminum behaves like copper

This calculator uses copper resistance. Aluminum has about 60% more resistance per gauge, so the same size will drop noticeably more. For aluminum, size up at least one gauge or use aluminum-specific values.

Note: This calculator gives an estimate, not a code-compliant design. Order about 10% extra wire for slack and splices, and have a licensed electrician verify any permitted work.

❓ Frequently asked questions

How is voltage drop calculated?

For a single-phase circuit, voltage drop is Vd = 2 x L x I x R / 1000, where L is the one-way distance in feet, I is the load current in amps, and R is the conductor resistance in ohms per 1000 ft. The 2 accounts for both the outgoing and return conductors. For a three-phase circuit you replace the 2 with the square root of 3 (about 1.732). Dividing the drop by the system voltage and multiplying by 100 gives the percent drop.

What is an acceptable voltage drop?

The National Electrical Code recommends (in an informational note, not a hard rule) keeping voltage drop to about 3% on a branch circuit, and no more than 5% total for the combined feeder and branch circuit. This calculator flags any result over 3% so you can upsize the wire before it becomes a problem.

Why does voltage drop matter?

Excess voltage drop wastes energy as heat in the wire and starves the load of voltage. Motors run hotter and lose torque, LED drivers can flicker or fail early, heaters and chargers run slowly, and sensitive electronics may misbehave. Long runs to a shed, well pump, EV charger or detached garage are the usual culprits.

Why do I enter the one-way distance instead of the total wire length?

Enter only the distance from the panel to the load. The formula already multiplies by 2 (single phase) to count the return conductor, so you do not double it yourself. If you measured the full round-trip length of wire, enter half of it.

How do I fix excessive voltage drop?

The most common fix is to use a larger conductor (a smaller AWG number has lower resistance). You can also shorten the run if the layout allows, reduce the load on that circuit, or in some cases raise the system voltage. This calculator suggests the next copper gauge that brings the drop back under 3% for your inputs.

Does this work for aluminum wire?

The built-in resistance values are for copper. Aluminum has roughly 60% higher resistance for the same AWG, so an aluminum conductor of the same size will show meaningfully more voltage drop. For aluminum, size up at least one gauge or use published aluminum resistance values and have an electrician verify.

What is the difference between single-phase and three-phase voltage drop?

Single-phase uses a multiplier of 2 (out and back). Three-phase balanced loads use the square root of 3 (about 1.732) because of how the phase currents and voltages combine. For the same current and distance, three-phase shows less line-to-line voltage drop than single-phase.

Does voltage drop affect the wire size I'm allowed to use?

Wire size is set first by ampacity - the conductor must safely carry the load current per NEC tables. Voltage drop is a separate, recommended check on top of that. A wire can be large enough for the current yet still drop too much voltage on a long run, in which case you upsize for the drop, not the ampacity.

What resistance values does this calculator use?

It uses approximate copper conductor resistances in ohms per 1000 ft: AWG 14 = 3.07, 12 = 1.93, 10 = 1.21, 8 = 0.764, 6 = 0.491, 4 = 0.308, 2 = 0.194, and 1/0 = 0.122. These are close to the values in NEC Chapter 9, Table 8 for stranded copper at about 75 degrees C.

Is this calculator a substitute for an electrician or the code?

No. It is a fast planning estimate. Final conductor sizing must satisfy ampacity, temperature, conduit-fill and termination limits, and should follow the current edition of the NEC and any local amendments. For permitted work, have a licensed electrician confirm the design.

How far can I run AWG 12 wire without too much voltage drop?

For single-phase copper AWG 12 (R = 1.93 ohms per 1000 ft) at the 3% limit, the maximum one-way run is about 62 ft at 120 V / 15 A, 47 ft at 120 V / 20 A, and 93 ft at 240 V / 20 A. Past those lengths, step up to AWG 10 or larger, or use a higher voltage.

How do you calculate three-phase voltage drop?

Use Vd = 1.732 x L x I x R / 1000, where 1.732 is the square root of 3, L is the one-way feet, I the amps, and R the ohms per 1000 ft. Example: a 480 V, 30 A load over 200 ft on AWG 6 copper drops about 5.10 V, or 1.06% - versus 5.89 V (1.23%) for the same run single-phase. Three-phase drop is always about 13.4% lower than single-phase for identical inputs.

๐Ÿ’ก Good to know

Distance and current hit equally hard

Voltage drop is proportional to both the run length and the current. Doubling either one doubles the drop. That is why a modest load 200 feet out can need the same wire as a big load 100 feet out.

Higher voltage reaches farther

At the same wattage, a 240 V circuit carries half the current of a 120 V circuit, so it loses half the percent of voltage on the same wire. Running 240 V where you can is often cheaper than upsizing the conductor.

Buy about 10% extra wire

Slack at the panel and the load, splices, and routing around studs and corners all add length. Order roughly 10% more than your straight-line estimate so you are not splicing a spool that came up short.

Related Calculators